Capacitance Humidity Probe

 

drawing.png


* Electrical characteristics

Humidity Sensor                      : VNCH-100

Supply voltage(Vin)                  : 5VDC

Current consumption                : MAX 1.3mA

Temperature coefficient             : -0.1 %RH/

Operation temperature              : -40 ~ 80

Operation humidity                  : 0 ~ 100%RH (non-condensing)

Voltage output                        : 0 ~ 3.3V (at 25, 0~100%RH Full scale)

Sensitivity                               : 31mV/%RH

Response time                         : 15 sec.

Humidity Accuracy                   : ±3%RH (at 25, from 20%RH to 90%RH)

Storage temperature range         : -40 ~ 90

Storage humidity range             : 0 ~ 100%RH

Typical output characteristics (Reference)  at 25, Vin = DC 5.0V     Unit :mV


RH (%)

10

20

30

40

50

60

70

80

90

95

Output

330

660

990

1320

1650

1980

2310

2640

2970

3135






* Standard Characteristics              

character.png


* Temperature Dependence(Reference)    : ±5%RH (Vin=5.0VDC, 30%RH to 80%RH,

                                                  Temp. Range 10 to 40(based on 25)

* Voltage Dependence(Reference)          : ±5%RH (Vin=5.0VDC, 30%RH to 80%RH,

                                                  Voltage Range 4.75 to 5.25VDC(based on 25)

 


 

 

* Mechanical characteristics

1. Shock resistance

Not to be abnormal in the appearance and electrical characteristics after having been

naturally let to drop down 3 times at random onto a hard wooden plate from the height of

100.

 

2. Vibration resistance

Not to be abnormal in the appearance and electrical characteristics after having been

vibration-tested for 2 hours each in the directions of X-Y-Z, at the frequency of 1055,

and amplitude of 1.5mm (10-55-10).

 

 

3. Resistance to soldering heat

Not to be abnormal in the appearance and electrical characteristics after lead terminal shall

be immersed down by 3mm from the substrate for 3 seconds in a solder bath of 260±5.

 

4. Strength of terminations (tensile)

Lead terminal shall be secured by the body after it shall be pulled with the specified force of

500g for 10 seconds in the axial direction of lead terminal.


 character 2.png

 




List of Articles
Humidity Sensor Module - VFC-1 imagefile
Electrical characteristics 1. Supply voltage(Vin) : ...  
Capacitance Humidity Probe imagefile
Capacitance Humidity Probe * Electrical characteri...  
Communication Transmitter imagefile
Communication Transmitter Communication Transmitter ...  
Differential Pressure Transmitter imagefile
Differential Pressure Transmitter Power In...  
Digital Hygro-Thermograph file
Digital Hygro-Thermograph  For Indoor Applicatio...  



XE Login